AMBIENT AIR MONITORING AQ-150

  • AMBIENT AIR MONITORING AQ-150


    The AQ-150 utilizes an optical layout consisting of an infrared emitter and silicon detector. As particles enter the sensing area an analog output, current or voltage, provides a signal which is proportional to the particle concentration.

    • Easy to install
    • Flexible design for fixed point monitoring.
    • Standard output of 4-20mA or optional 0-1V output
    • Adjustable alarm
    • Light weight and durable construction
    • Graphic LCD Display with read out in mg/m³
    • Optional NEMA 4X housing or Explosion Proof Enclosure

Description

AQ-150 is suitable for monitoring particulate emissions from cyclones, precipitators, bag houses, or any dust control device. It is also ideal for monitoring air quality in underground transportation systems, ventilation systems, indoor workplaces, or any other application where immediate data on smoke, dust, fumes, or mists is needed. AQ-150 warns you of problems before they become trouble.

AQ-150 utilizes an optical layout consisting of an infrared emitter and silicon detector. As particles enter the sensing area an analog output, current or voltage, provides a signal which is proportional to the particle concentration. The signal can be sent to a recorder or central processing panel.

AQ-150 easily mounts on walls, inside air ducts or at strategic locations in dust collectors, bag houses, or any dust control device. Units can be configured in a single or multipoint system.

If your company generates oremits particulate matter, then the AQ-150 will enhance your air monitoring requirements and assist your company in complying with Regulations.

Specification

Sensing Range0.01-200 mg/m³ (standard)
0.1-2000 mg/m³
0.001-20mg/m³ (optional),(for other, please contact HNL)
Particle size range0.1-50 μm
Precision+/- 0.02 mg/m³ or +/- 0.004 mg/m³
Power110 or 220 V AC; 12 V DC wall transformer (optional)
Signal output4-20 mA; 0-1 Volt (optional)
Alarm output7 V DC
Operating temperature0 – 65°c
Humidity95% non-condensing
Dimensions7.5″ x 4.5″ x 4″ approx
Weight2Kg

Note : Specifications and Features will vary with application. The above are established and validated during design, but are not to be construed as test criteria for every product. Due to hnl’s commitment to research, design and product improvement, specifications are subject to change without notice.